OHA Drinking Water Services

OHA Drinking Water Services
Water Advisory Details

PWS ID: OR41 95127
PWS Name: SALMON RUN GOLF COURSE
 
Advisory Type: Boil Water
Reason: Loss of Pressure
Area Affected: System-wide
Affected Populations: All
 
Begin Date: May 08, 2020
Date Lifted: Jun 12, 2020
 
Contacted By: DOWNS, KENT (DWP)
Who Was Contacted: MARK HAGLUND
Contact Phone: 541-412-0424 ext 7
 
Details: Operator posted a boilwater notice on Friday, May 8,2020 due to loss of pressure. The system was taken off-line and connected to a new drilled well. The new well is currently being evaluated and tested. The distributions lines were flushed and the system is espected to be back on-line next week (May 13). On this date the operator plans to test the water quality in the distribution lines to ensure abcense of colifrom bacteria. The boil water advisory will be removed when the distribution water sample test result shows an abscence of coliform bactiera. However, the operator was instructed not to use the new source until a raw water sample is colleted and tested for Arcenic, Nitrate and Coliform Bacteria. Operator was also instrcuted to provide copy of the plan review approval by the DWS Office.

Lifted 06/12/2020:  Water system tested for Arsenic, Nitrate and coliform bacteria. Arsenic and Nitrate levels are acceptable. No E. coli or TC found in the distribution sample. New Well (SRC AB) tested absent for E. Coil, but positive for TC. However, the UV reactor is maintaining the minimum 4 log disinfection in the distribution line.

Associated Alerts: COLI19923 - 06/12/2020 - COLIFORM (TCR)



More information for this water system: SDWIS ID 4655
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login