OHA Drinking Water Services

OHA Drinking Water Services
Water Advisory Details

PWS ID: OR41 93750
PWS Name: WILLOWCREEK ELEM SD #84
 
Advisory Type: Do Not Drink Water
Reason: Arsenic
Area Affected: System-wide
Affected Populations: All
 
Begin Date: Feb 07, 2018
Date Lifted: Feb 20, 2018
 
Contacted By: GOSS, BILL (DWP - PENDLETON)
Who Was Contacted: Alisha McBride
Contact Phone: 541-473-0201
 
Details: Arsenic result from a sample collected on January 24, 2018 came back at 0.0691 mg/l, which is above the acute arsenic limit. Discussion with the treatment system installer revealed the arsenic removal media in the treatment system is exhausted and must be replaced. Media replacement is scheduled for February 12-13. Drinking Water Warning notice to be posted at the school and sent home with the students.

Lifted 02/20/2018:  The media in the arsenic removal system was replaced. A sample collected on 2/14/18 tested non-detect for arsenic, allowing the drinking water advisory to be lifted.

Associated Alerts: CHEM7859 - 02/06/2018 - ARSENIC



More information for this water system: SDWIS ID 3081
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login