OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00029
PWS Name: PERIWINKLE MOBILE HOME PARK
 
Who Was Contacted: GARREN FRIEDEMANN
Contact Phone: 541-505-9968 (Email address hidden)
Contact Date: 05/16/2022
Contacted By: BAIRD, GREGG (DWP)
Contact Method/Location: Email
 
Assistance Type: OTHER WATER QUALITY - PFAS confirmation sample results
Reasons: Other
 
Details: A confirmation sample collected 4/4/22 as part of the OHA-DWS PFAS Sampling Project showed PFOS at 16.3 ppt and PFHxS at 12.5 ppt at entry point A (EP-A). The confirmation sample results are almost identical to the original sample results and the sum of the two detection is 28.8 ppt which is below Oregon's 30 ppt drinking water health advisory level (HALs) for PFOS, PFOA, PFNA, and PFHxS (individually or combined). Since neither the original or confirmation sample results exceeded the health advisory level, OHA recommends sharing the results with customers, including results in the annual Consumer Confidence Report, and testing the drinking water for PFAS periodically. Although the sum of the concentrations of PFOS and PFHxS does not exceed the 30 ppt Oregon drinking water health advisory level, it’s really close to exceeding it. Given that, and the fact that EPA is expected to propose a low drinking water maximum contaminant level for PFOS by the end of this year, I recommended starting to think about some kind of corrective action (connecting to another public water system, developing a new drinking water source, or installing treatment to remove PFAS). A letter and the sample results were mailed to the water system on 5/13/22 and emailed on 5/16/22.


More information for this water system: SDWIS ID 3220
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login