OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 95508
PWS Name: PGE TROJAN PARK
 
Who Was Contacted: Keith, Veolia Water
Contact Phone: 503-266-6400
Contact Date: 08/03/2022
Contacted By: OSBORN, DANIEL (COLUMBIA COUNTY)
Contact Method/Location: Phone
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
 
Details: I spoke with Keith from Veolia Water who works with Brian Hutchins; we discussed that on Monday 8/1 a water sample was collected from PGE Trojan Park's well after the Repeat samples which came back positive for total coliform. There was a mouse nest discovered in the corner of the well house, and it was also determined that the wellhead's vent did not have a screen secured on it.
We discussed how no pesticides or rodenticides or any chemicals are to be sprayed within the wellhouse or even within 50 feet of it, but physical removal of the mouse nest and mice will be required. The vent will need to be screened, and some type of material buffer around the wellhouse lid, screen or other material, is advised to prevent rodent entry. Keith says he plans to go back out to the location and put a mesh screen over the wellhouse opening, and secured around the wellhead's vent, as well as removing the mouse nest. Keith also says that Veolia Water will collect the follow up samples as well.
Since a source well sample was collected voluntarily on August 1st, I mentioned I would see if that could be included as one of the 3 routine coliform samples regarding the month following the positive total coliform result.
 
Associated Alerts: COLI22362 - 07/28/2022 - COLIFORM (TCR)   See also: 07/28/2022

COLI22352 - 07/26/2022 - COLIFORM (TCR)   See also: 07/26/2022



More information for this water system: SDWIS ID 5330
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login