OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 91511
PWS Name: SHADY COVE MIDDLE SD #9
 
Who Was Contacted: John Harding
Contact Phone: 541-830-6376
Contact Date: 04/29/2022
Contacted By: CIVIL WEST ENGINEERS, INC (DWP)
Contact Method/Location: Phone
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
 
Details: Background/Problem Identification:

The circuit rider was contacted by John Harding of Eagle Point School District on 03/15/2022 regarding having a corrosion control method selected and in place if they exceed the MCL for lead again. After several weeks with no response, a new circuit rider support effort was opened when J. Harding reached back out on April 29th, 2022.

Assistance Provided:

The circuit rider received both requested rounds of WQP from John on 05/09/2022. The results of the WQP tests are summarized and averaged in the table below:

Room 10 4/12/22 Staff Sink 4/12/22 Girl's Locker 4/12/22 Boy's RR 4/12/22 Room 10 4/26/22 Staff Sink 4/26/22 Girl's Locker 4/26/22 Boy's RR 4/26/22 AVERAGE
Sp. Conductance 386 383 418 422 394 395 429 731 445
~TDS 257 255 279 281 263 263 286 487 297
Alkalinity - ppm 170 170 184 188 168 168 180 186 177
Calcium - ppm 15.2 14.7 7.6 7.7 14.3 14.6 7.4 5.7 10.9
pH 8.5 8.2 8.1 8.5 8.2 8.6 8.3 8.4 8.4
Temperature - oC 14.7 16.0 16.8 17.5 14.4 15.0 16.3 17.9 16.1
DIC (Appx. B est.) 41 42 45 45 40 39 43 45 43
Target saturation pH = 8.2

Based on the available data and employing the EPA OCCT’s recommendations for corrosion control, Flow chart 1c calls for raising pH with caustic soda in 0.3 increments to a pH of 9.0 – 9.5. The other method is to inject orthophosphate. Using caustic soda to raise the pH may cause scaling. The orthophosphate method would likely need pH adjustment to ~7.5 in order to get in the pH range where orthophosphate works best. We recommend using the caustic soda method first, and only if the scaling is too excessive that the system switch to the pH adjustment/orthophosphate method.

Follow-Up Actions Needed:

The circuit rider is available to assist further if need be.

Technical Reports to be Prepared and Expected Timeframe:

N/A



More information for this water system: SDWIS ID 899
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login