PWS ID: OR41 05860
PWS Name: OLD SHEEP RANCH WATER ASSOC
 
Who Was Contacted: Mark Ochsner
Contact Phone: 503-501-7553 (Email address hidden)
Contact Date: 10/06/2022
Contacted By: DOWNS, KENT (DWP)
Contact Method/Location: Phone
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
 
Details: Failure to meet WQP in September
An excursion occurred when the daily pH value measured at the entry point was below the minimum value ( 7.2) set by DWS. Unfortunately, no additional pH measurements were taken for the next 12 days after the excursion on 9/18. Each additional day without test results for pH and alkalinity counted as an additional excursion for a total of 13 excursions.

Mark was instructed to take the following steps:

1. Issue a Tier 2 public notice. A Tier 2 public notice template was provided via email. The notice must be posted as soon as practical using the following methods: Hand or direct delivery, mail, as a separate notice, or included with the bill.

2. Email me a copy of the public notice with the date posted. The notice must remain posted at least seven days, or until the issue that caused the violation is resolved.

3. Collect two rounds of lead and copper in the distribution system. Round one must be collected between January 1 and June 30, 2023. Round two between July 1 and December 31, 2023. Lead and copper samples must be collected at the same 5 homes used in previous years for lead and copper sampling.

4. The operator was reminded to measure pH and alkalinity in the distribution system during the lead and copper sampling and also two weeks after each round of lead and copper sampling.

Recommended sampling pH and alkalinity at least once every week, but never less than once every 14 days.
 
Associated Alerts: LCRE31631 - 10/06/2022 -   See also: 10/12/2022



More information for this water system: SDWIS ID 2082
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login