Contact Report Details

PWS ID: OR41 95478
PWS Name: REEHERS HOMESTEAD INC
 
Who Was Contacted: Christine Chambreau
Contact Phone: 801-550-2665
Contact Date: 07/06/2022
Contacted By: CIVIL WEST ENGINEERS, INC (DWP)
Contact Method/Location: Field
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
 
Details: Background/Problem Identification:

The circuit rider was contacted by OHA and was requested to assist with assessment of the source and storage systems with respect to construction to exclude surface water, & the possibility of installing continuous disinfection.

Assistance Provided:

The circuit rider visited the water system on 7/29/22 to assess the water system, specifically the source and the storage systems. As indicated by Christine Chambreau, the latest (07/10/22) coliform sampling on the source was negative. Sampling in distribution five days (07/05/22) prior was positive. Many unscreened entrances to the storage tanks & recommended cleaned & screened.

Most recent test was negative for coliform in the spring source, the spring source does have a history of positive coliform tests. Discussed potential methods to meet OVS treatment requirements with the water system.

1 option for treatment was addition of bag/cartridge filtration (Harmsco Hurricane H-170 or equivalent) to sub-micron levels coupled with a Dosatron chlorinator. No power @spring source or storage area, & unless power run to the area, a bag/cartridge filter & Dosatron would be only means to comply OVS treatment w/o power.

If the water system was willing to install treatment closer to an existing source of power, but still on the transmission main between the storage tanks and the distribution system, a UV system and powered chlorination system could be employed. For this alternative, we recommend installing a UV system and chlorination to comply with OVS regulations. The UV system NSF Standard 55, &e Class A. The Viqua Pro30 UVMax system satisfy the OVS treatment requirement. Recommend 30gpm unit installed w/flow restrictor to limit flow to <30 gpm. Residual maintenance disinfection achieved using low-paced dosing pump/meter ie-Stenner Econ-FP series system. recommend small mixing tank place after the injection point to allow for mixing of the pulsed injections.

Avail assist if needed.


More information for this water system: SDWIS ID 5289
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login