OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00554
PWS Name: NEHALEM, CITY OF
 
Who Was Contacted: Brian Moore
Contact Phone: 503-368-5155 (Email address hidden)
Contact Date: 11/15/2022
Contacted By: HOFELD, EVAN (DWP)
Contact Method/Location: Email
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Disinfection Byproducts
 
Details: I received an alert on 11/14/22 (Monday) for elevated HAA5 results from sampling on 11/1/22 at sample location “SM-2 - 13405 THOMPSON RD” which was 0.0865 mg/l. Although the individual result was over 0.060 mg/l, this did not result in an Operational Evaluation Level (OEL) or Maximum Contaminant Level (MCL) exceedance based on a locational running annual average (LRAA). For 4th quarter 2022, the OEL based on the 11/1/22 sample for HAA5 was 0.056 mg/l and the HAA5 LRAA was 0.042 mg/l. The TTHM OEL was 0.060 mg/l and the TTHM LRAA was 0.049 mg/l for 4th quarter 2022. DBP levels for Nehalem have had seasonal variations and have been in this range before. I e-mailed Brian Moore with Nehalem about the results and although no further action is required at this time, I asked him why the results may have been higher this time. 11-15-22 update by Evan Hofeld (OHA-DWS) - Brian Moore e-mailed back on 11-15-22 indicating that there were no treatment issues and that he thought the elevated results were just due to seasonal source water quality changes.
 
Associated Alerts: CHEM9989 - 11/14/2022 - TOTAL HALOACETIC ACIDS (HAA5)



More information for this water system: SDWIS ID 3975
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login