Who Was Contacted: Brad Daniels
Contact Phone: 503-735-5438 (Email address hidden)
Contact Date: 11/30/2022
Contacted By: HOFELD, EVAN (DWP)
Contact Method/Location: Email
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
 
Details: I emailed Brad Daniels on 11-30-22 to add the date lead public education was distributed (11-3-22) and the date that the water system operator (Justin Hartford) e-mailed us the results of their corrosion control treatment evaluation on 11-19-22 that they conducted with the assistance of the SRF technical Assistance Circuit Rider (Dan Vaage, PE with Civil West). Per Justin: the soda ash pump sight glass had been worked on prior to his hire at Hebo and needed the correct part, which he ordered, to make sure everything was running correctly. Also while the engineer (Dan Vaage) was there they determined that they were not getting the correct dosing of soda ash due to low flows during the summer months. They have a 4” flow meter and the dosing pumps would start and stop sporadically and not dose the proper amount of soda ash. Their solution to help with low flows is to look into and order a smaller flow meter so when flow get low their chemical pumps will be able to dose more consistently. Now that the springs are full and running at full capacity their alkalinity numbers have dropped to between 60-80 mg/l and their pH was between 7.4-7.7. Justin plans on taking Lead and Copper samples in the beginning of December to see if the levels have gone down at all.
 
Associated Alerts: CHEM9960 - 10/25/2022 - COPPER SUMMARY , LEAD SUMMARY   See also: 10/25/2022



More information for this water system: SDWIS ID 4318
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login