OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 95478
PWS Name: REEHERS HOMESTEAD INC
 
Who Was Contacted: Christine Chambreau
Contact Phone: 801-550-2665
Contact Date: 07/06/2022
Contacted By: CIVIL WEST ENGINEERS, INC (DWP)
Contact Method/Location: Phone
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
 
Details: Background/Problem Identification:
The circuit rider (CR) was contacted by OHA &requested to assist with assessment of the source & storage systems with respect to construction to exclude surface water, & possibility of installing continuous disinfection.

Assistance Provided:
The CR visited the water system on 7/29/22 to assess water system, specifically source & storage systems.Indicated by Christine Chambreau, latest (07/10/22) coliform sampling on the source was negative. Sampling in distribution five days (07/05/22) prior was positive. The CR noted were many unscreened entrances to storage tanks &recommended be cleaned & screened.

Although the most recent test was negative for coliform in the spring source, the spring source does have a history of positive coliform tests. The CR discussed potential methods to meet new OVS treatment requirements with the water system.

One option for treatment was the addition of bag/cartridge filtration (Harmsco Hurricane H-170 or equivalent) to sub-micron levels coupled with a Dosatron chlorinator. There is no power at spring source or storage area, & unless power run to the area, a bag/cartridge filter & Dosatron system would likely be the only means to comply with the OVS treatment without power.

If the water system was willing to install treatment closer to an existing source of power, but still on the transmission main between the storage tanks and the distribution system, a UV system and powered chlorination system could be employed. For this alternative, we recommend installing a UV system and chlorination to comply with OVS regulations. The UV system shall meet NSF Standard 55, and be Class A. The Viqua Pro30 UVMax system would satisfy the OVS treatment requirement.Recommend a 30gpm unit installed w/flow restrictor to limit the flow to <30 gpm. Residual maintenance disinfection can be achieved using a flow-paced dosing pump/meter ie the Stenner Econ-FP series system. We recommend a small mixing pulsed injections.


More information for this water system: SDWIS ID 5289
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login