OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 91967
PWS Name: CAMP TILIKUM
 
Who Was Contacted: Justin Adsit
Contact Phone: -- (Email address hidden)
Contact Date: 04/14/2023
Contacted By: ALFAFARA, NICOLE (DWP)
Contact Method/Location: Email
 
Assistance Type: VIOLATION RESPONSE
Reasons: Chlorine
SWTR
 
Details: The system was out of compliance for both entry point minimum chlorine residual and meeting CT in both January and February of 2023. In February and March, DWS Staff reached out to the system with support and guidance on the following topics: updating system contact information (new Maintenance Director), the monthly reporting deadline, EPA Table usage and CT calculations and PN requirements. System notified DWS staff of recent staffing changes and stated the chlorine dosing pump had an inadequate amount of solution to draw from for several weeks and consequently chlorine residuals dropped. The tank storing the chlorine solution was replenished and protocols have been put in place to check the chlorine solution levels in the dosing tank every day the system is in operation. The March 2023 SWTR was submitted on time and system met CT and the minimum chlorine residual. Consequently, the 4 violations RTC.
 
Associated Violations: Viol #900752320, 02/01/2023 - 02/28/2023: SWTR - Failure to Maintain EP Disinfection

Viol #900752321, 02/01/2023 - 02/28/2023: SWTR - Failure to Meet CT

Viol #900752318, 01/01/2023 - 01/31/2023: SWTR - Failure to Maintain EP Disinfection

Viol #900752319, 01/01/2023 - 01/31/2023: SWTR - Failure to Meet CT



More information for this water system: SDWIS ID 3017
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login