OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00552
PWS Name: BRIDGE WATER DISTRICT
 
Who Was Contacted: Daniel Horner
Contact Phone: 541-290-9661
Contact Date: 12/05/2018
Contacted By: PARRY, BETSY (DWP)
Contact Method/Location: Phone
 
Assistance Type: VIOLATION RESPONSE
Reasons: SWTR
 
Details: The repeat coliform samples were absent, so the Nov. 29 EC+ test result will not cause a violation. I learned that this sample had been collected before the disinfection contact chamber, so that it did not represent the treated water. Routine coliform samples are supposed to represent the quality of the water in the distribution system, post-treatment. We discussed revising their coliform sampling plan to eliminate this location as a routine site, and that they specify repeat sampling locations corresponding to each routine site. He may retain the repeat location of just after the storage tank if he chooses, to represent the "upstream" repeat location.

However, they also did not meet CT for two days in late November. Daniel said that scale had gotten into the tube of the Stenner chlorine feed pump, causing the dosage to drop, so he cleaned out the tube. He also said it had happened before. I strongly recommended that they figure out how to avoid this happening in the future as this is crucial to meeting the disinfection standard and avoiding future violations. Not meeting CT for two days in November will result in a Treatment Technique violation. I emailed Daniel a recap of all this information and included the template for this public notice. He said he will include this notice with the monthly bills which are about to be mailed to residents.
 
Associated Violations: Viol #, - : -



More information for this water system: SDWIS ID 4050
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login