OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00556 | ||
PWS Name: | NETARTS WATER DISTRICT | ||
Who Was Contacted: | David Hancock | ||
Contact Phone: | 503-842-9405 | ||
Contact Date: | 01/10/2023 | ||
Contacted By: | CIVIL WEST ENGINEERS, INC (DWP) | ||
Contact Method/Location: | Field | ||
Assistance Type: | CIRCUIT RIDER ASSISTANCE | ||
Details: | Background/Problem Identification: Evan Hofeld of OHA reached out to the circuit rider indicating that Netarts Water District needed assistance with a recommendation for corrosion control for their spring source. Assistance Provided: The circuit rider analyzed the system’s WQPs and used the EPA OCCT to select a corrosion control method. Based on the spring source WQP available from the water treatment plant operator, (pH=6.27, alk=84 mg/L, Ca=34 mg/L (estimated), DIC=39, no Fe or Mn) the EPA OCCT recommended flowchart is 1a. Our recommendation is that the spring source should be treated with soda ash and the pH raised in 0.25-unit increments (until the corrosion issues subside) up to the theoretical CaCO3 saturation pH of ~7.7. Follow-Up Actions Needed: The circuit rider is available to assist further as needed. Technical Reports to be Prepared and Expected Timeframe: N/A |