OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 95229
PWS Name: CAMP ATTITUDE
 
Who Was Contacted: Tim Walisiak
Contact Phone: 541-619-0565
Contact Date: 03/17/2023
Contacted By: CIVIL WEST ENGINEERS, INC (DWP)
Contact Method/Location: Field
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
 
Details: Background/Problem Identification:

The water system is fed by one well (Well #2 “L116339”). The well has a seasonal history of positive hits for coliform and needs help to find the cause.

Assistance Provided:

The circuit rider made a site visit to assess the well and identify possible causes for the seasonal coliform issues. T. Walisiak explained that coliform issues typically occur during the summertime when the water system is seeing it’s highest demands.

It was noted during the site visit that the well is not vented. There is a possibility that during high demands the well may be creating a vacuum (low pressure) condition due to the lack of a vent, and this may be “pulling” surface water (or other unconfined groundwater) down past the well seal and into the well. The circuit rider recommends that a downwards facing screened vent be installed on the well head to eliminate this possibility of coliform intrusion.

Further the circuit rider noticed what looked to be animal droppings in the well house. The well house should be thoroughly cleaned and the means of rodent/insect entry should be found and eliminated.

Follow-Up Actions Needed:

The circuit rider can assist further as needed.

Technical Reports to be Prepared and Expected Timeframe:

N/A


More information for this water system: SDWIS ID 4872
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login