OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00386
PWS Name: CRYSTAL SPRINGS WATER DISTRICT
 
Who Was Contacted: Fred Schatz
Contact Phone: 541-399-3926 (Email address hidden)
Contact Date: 09/01/2023
Contacted By: HOFELD, EVAN (DWP)
Contact Method/Location: Email
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Nitrate
 
Details: On 8/30/23 I received an alert for nitrate at 5.42 mg/l from EP-B (Davis/Odell Spring) for a sample taken 8/15/23. The system has been on quarterly monitoring for 1-year beginning 10/1/22 to determine if the source is reliably and consistently below the 10 mg/l MCL for nitrate. This result is the 4th of 4 quarterly samples needed. Results for the 4 quarterly sample dates are as follows: 11-2-22 - 6.72 mg/l, 2-14-23 - 7.38 mg/l, 6-6-23 - 6.35 mg/l, 8-15-23 - 5.42 mg/l. Results demonstrate EP-B is reliably and consistently below the nitrate MCL of 10 mg/l, therefore, sampling may be reduced from quarterly to once per year. Sampling is to be done in the first calendar quarter of each year (January 1st - March 31st) since that is the quarter with the highest quarterly sample result (7.38 mg/l on 2-14-23). I e-mailed Fred Schatz a link to this contact report, submitted the chemical monitoring change form to update the sampling schedule, and let Fred know that annual sampling could begin in the 1st quarter of 2024. I also followed up with a phone call to see if he had any questions.
 
Associated Alerts: NO3-122 - 08/30/2023 - NITRATE



More information for this water system: SDWIS ID 4230
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login