PWS ID: OR41 94300
PWS Name: ROSEBURG FOREST PROD - DILLARD
 
Who Was Contacted: Nate Webb
Contact Phone: 541-679-2695
Contact Date: 09/07/2023
Contacted By: TEMPLIN, REBECCA (DWP)
Contact Method/Location: Field
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Disinfection Byproducts
 
Details: During the survey field visit on 9/7/2023 I spoke with Nate about the recent high TTHM result for the system. The result was 0.0913 mg/L for the TTHM and MCL is 0.0800 mg/L. The sample was taken on 8/03/2023 (3Q). And the current locational running annual average (LRAA) for the system is now 0.0570 mg/L, which is below the MCL. Since the LRAA is what is used for regulations, the system is not out of compliance. I discussed the options with the system about making operational changes if the problem persists and they should let me know if they need any help coming up with ideas. At this point no further action is required until the LRAA exceeds the MCL.
 
Associated Alerts: DBP-18 - 08/10/2023 - TTHM



More information for this water system: SDWIS ID 3197
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login