OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 01308
PWS Name: TRAPPIST ABBEY
 
Who Was Contacted: Jose Montoya
Contact Phone: 503-852-7174 ext 1271
Contact Date: 12/31/2018
Contacted By: DANIELS, BRAD (DWP)
Contact Method/Location: Phone
 
Assistance Type: OTHER REGULATORY - Discussed E. coli positive assessment sample
Reasons: Coliform
 
Details: I called Jose to notify him that a source assessment sample, collected on December 28, 2018, was E. coli positive and that five confirmation samples must be collected from the spring as soon as possible. Jose stated it is unlikely he can collect the samples today because he doesn't have enough sample bottles but I stated samples collected this week would be acceptable. Jose mentioned the spring is about one quarter of a mile away and that the waterline from the spring flows past the valve for well #2, which is inactive. From Jose's description, it's possible stagnant water from well #2 is causing the bacteria to be present in samples from the spring. Jose also described it is difficult or impossible to collect samples directly from the spring itself because it's buried beneath the ground. I recommended to Jose that the inability to collect samples directly from the spring and the possible mixing with water standing in well #2 are issues that should be resolved in the future. For the time being, Jose will collect the confirmation samples from the source and consult with Dept. of Agriculture about further response.
 
Associated Alerts: COLI18582 - 12/31/2018 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 4139
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login