OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 95593
PWS Name: MAYSARA WINERY
 
Who Was Contacted: Moe Momtazi
Contact Phone: 503-843-1234 (Email address hidden)
Contact Date: 01/08/2019
Contacted By: SCHWAB, SARAH (DEPT OF AGRICULTURE)
Contact Method/Location: Phone
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
 
Details: An alert was issued because two of the three temporary routine samples came back total coliform present at the tasting room sink and bathroom sink. The firm plans to treat the cement storage tank with chlorine for 24 hours and then flush the system. It was suggested to take one distribution sample at the bathroom sink or tasting room sink after the chlorine is flushed out of the system. This sample could be marked as 'special' on the lab report so that it is used for the firm's information only and not a regulatory sample. If this ‘special’ sample comes back absent, then the firm will need to take three ‘routine' samples in the month of February: one at the kitchen sink, one at tasting room sink, and one at restroom sink. If the ‘special’ sample is present then the firm will need to continue to investigate the cause and a correction for the issue.

The coliform level 1 investigation form was emailed to Moe Momtazi and the deadline to get that turned in was discussed. We also discussed an onsite level 2 investigation that would be scheduled in the near future.
 
Associated Alerts: COLI18601 - 01/07/2019 - COLIFORM (TCR)



More information for this water system: SDWIS ID 5467
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login