OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00692
PWS Name: PRESCOTT, CITY OF
 
Who Was Contacted: Jim Oswald
Contact Phone: 503-396-3580
Contact Date: 02/29/2024
Contacted By: OSBORN, DANIEL (COLUMBIA COUNTY)
Contact Method/Location: Phone
 
Assistance Type: OTHER REGULATORY - Proposed Storage & Contact Tank flushing
Reasons: Operations
 
Details: I spoke with Jim Oswald about City of Prescott's plans to have the interiors of two 10,000 gallon storage tanks and the one 3,000 gallon contact tank pressure washed, and have the debris vacuumed out. We discussed the required disinfection of the tanks after these procedures, as well as collecting a total of 3 water samples, each being representative of a corresponding tank (total of 3 samples), to test for total coliform bacteria as well as the chlorine level after post-chlorination flushing.
Days prior, I forwarded Jim the sections in the rules listing the options the system may choose for the required tank disinfection after the flushing and cleaning, which is OAR# 333-061-0050 section (10) segments (e) through (i) for reference.
Jim told me Prescott has decided to go with the spraying option of higher chlorinated water rather than filling the tank with lower chlorinated water and letting it sit for hours. Jim added that the company doing the pressure washing and vacuuming also said they can collect and dispose of the chlorinated solution in an approved containment location, using their equipment, rather than discharging it all onto the ground.


More information for this water system: SDWIS ID 3986
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login