OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00731
PWS Name: SALEM PUBLIC WORKS
 
Who Was Contacted: Lacey Goeres-Priest
Contact Phone: 503-361-2224 (Email address hidden)
Contact Date: 06/11/2024
Contacted By: BAIRD, GREGG (DWP)
Contact Method/Location: Phone
 
Assistance Type: MONITORING
Reasons: Cyanotoxins
 
Details: Lacey notified OHA that total microcystins were detected at 0.604 ug/L in a raw water sample collected Monday 6/10/24 and at 0.468 ug/L in a sample collected Tuesday 6/11/24 (both samples were analyzed by their lab on 6/11/24). As a result, required raw water monitoring frequency has been increased to weekly. An entry point (finished water) sample must be collected within 1 business day and entry point monitoring continue weekly going forward. Informed Lacey of monitoring schedule change and she confirmed they will collect and analyze a finished water sample Wednesday 6/12/24. Salem voluntarily monitors raw water more frequently than required by rule (currently 5 times a week). They have been operating their ozone treatment all season and plan to increase the dose, as well as increase their post-chlorination dose. Update 6/13/24: finished water sample from yesterday 6/12/24 was non-detect. Update 7/15/24: OHA recommended all downstream PWSs increase chlorine residuals and review optimization guidance due to elevated levels of raw water microcytins reported by Salem for sample collected Sunday 7/14/24 (14.332 ug/L). Checked in with Lacey and she indicated staff are managing the incoming toxin by utilizing roughing filters, ozone, finished filters, and chlorination and treatment seems to be working well.


More information for this water system: SDWIS ID 3906
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login