OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05592
PWS Name: BOB BELLONI RANCH
 
Who Was Contacted: David Orchard
Contact Phone: 541-260-3009
Contact Date: 01/23/2019
Contacted By: PARRY, BETSY (DWP)
Contact Method/Location: Phone
 
Assistance Type: MONITORING
Reasons: Disinfection Byproducts
 
Details: David Orchard (on site operator) phoned asking whether BBR could now get a reduction in the DBP sampling schedule. Because the average of the last 4 quarters is low enough, yes, they can. I sent the change request to our data entry folks.

The new DBP monitoring schedule will be one dual sample per year, collected in the month of September. September has typically been one of the highest months on record for DBPs – probably because the water flow is low/less dilution, plus there’s high organic content with the leaf fall.

The lower results that David has achieved since assuming the operator's role are impressive. I expect that dialing down the amount of pre-chlorination, and adding back the post-chlorination application has made a big difference.

David also asked about calibrating their turbidimeter because Hach notified them they are increasing their fee for that service. David has seen instructions in the Hach owner's manual. We discussed that they will need a set of primary calibration standards to do it themselves, and these expire each year. It is also possible to make one's own calibration standards, if an operator invests in the products needed to make them and is willing to put in the time and effort. David will look into it. David is currently studying to take the Level 1 operator's exam.


More information for this water system: SDWIS ID 3924
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login