OHA Drinking Water Services 
		Contact Report Details  |  
	|||
| PWS ID: | OR41 00028 | ||
| PWS Name: | OAKVILLA MOBILE HOME PARK | ||
| Who Was Contacted: | Annette Cistone | ||
| Contact Phone: | (Email address hidden) | ||
| Contact Date: | 06/20/2024 | ||
| Contacted By: | KIRKLEY, STEPHEN (LINN COUNTY) | ||
| Contact Method/Location: | |||
| Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
| Reasons: | Nitrate | 
	||
| Details: | Hello, @OAKVILLAMHP@GMAIL.COM, Your water system recently had a lab test come back high in Nitrate. The nitrate alert level is greater than half of the maximum contaminant level (MCL). MCL for Nitrate = 10 mg/L ½ MCL for nitrate = 5 mg/L Results: EP-A 6.9 mg/L EP-B 7.0 mg/L Your system is now required to test nitrate quarterly. Once there are three consecutive quarterly samples that are below the 1/2MCL, your system can return to annual nitrate testing. @OHA Compliance - Attached is the chemical schedule form to increase nitrate sampling to monthly.  | 
||
| Associated Alerts: | NO3-284 - 06/20/2024 - NITRATE                                  NO3-285 - 06/20/2024 - NITRATE  | 
	||