Details: Hello, @OAKVILLAMHP@GMAIL.COM,
Your water system recently had a lab test come back high in Nitrate. The nitrate alert level is greater than half of the maximum contaminant level (MCL).
MCL for Nitrate = 10 mg/L
½ MCL for nitrate = 5 mg/L
 Results:
EP-A 6.9 mg/L
EP-B 7.0 mg/L
Your system is now required to test nitrate quarterly. Once there are three consecutive quarterly samples that are below the 1/2MCL, your system can return to annual nitrate testing.
@OHA Compliance - Attached is the chemical schedule form to increase nitrate sampling to monthly.
 
Associated Alerts: NO3-284 - 06/20/2024 - NITRATE

NO3-285 - 06/20/2024 - NITRATE