OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 91205 | ||
PWS Name: | MARIAL LODGE | ||
Who Was Contacted: | Amber Biscarret | ||
Contact Phone: | (Email address hidden) | ||
Contact Date: | 07/24/2024 | ||
Contacted By: | DOWNS, KENT (DWP) | ||
Contact Method/Location: | |||
Assistance Type: | OTHER REGULATORY - Completed Level 2 Coliform Investigation | ||
Reasons: | Coliform |
||
Details: | Level 2 coliform investigation completed on 07.24.2024. The failure of the chlorine injection pump was identified as the main cause of the multiple E. Coli samples. Next steps: The chlorine injection pump was fixed, and the chlorination system is back online. The operator should verify free chlorine concentration is recorded when coliform samples are collected. Recommend using a non-swivel type faucet for coliform sampling to prevent cross contamination. Swivel joints on the faucet can harbor bacteria, creating the potential for bacterial contamination during sample collection. |
||
Associated Alerts: | TCR-2319 - 07/15/2024 - E. COLI TCR-2320 - 07/15/2024 - E. COLI TCR-2316 - 07/15/2024 - COLIFORM (TCR) TCR-2317 - 07/15/2024 - COLIFORM (TCR) TCR-2318 - 07/15/2024 - E. COLI TCR-2314 - 07/15/2024 - COLIFORM (TCR) TCR-2315 - 07/15/2024 - COLIFORM (TCR) |