OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 93429
PWS Name: KIMBALL CREEK BEND RESORT
 
Who Was Contacted: Toby Bowman
Contact Phone: (Email address hidden)
Contact Date: 10/09/2024
Contacted By: DOWNS, KENT (DWP)
Contact Method/Location: Email
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
 
Details: TCR-2816

10.09.2024-Operator submitted L1 Coli investigation report. Report submitted to DMCE. TG sample came back absent of coliform contamination. No further actions needed at this time.

10.03.2024-Only the repeat sample collected at initial site that tested positive for TC came back TC positive. Next steps:

- The operator was instructed to collect a TG sample. TG sample will be collected prior to any corrective actions. The operator is planning to replace the sample tap at the Hydrant R6 sample site. Once the tap is replaced, the operator will shock the system and collect a special sample. A level one coliform investigation will be conducted. L1 coliform investigation form submitted to operator.

09.26.2024- The RT sample collected on 08.23.24 tested positive for TC. The operator investigated the caused of the TC positive. The control panel went out and the chlorinator was unplugged, indicating a potential loss of disinfection. The chlorinator has been resorted to operation.

Next steps: The operator was instructed to collect 3 repeat samples and one triggered sample. The TG sample will count as the AS sample for 2024.

Additional information provided: A coliform sampling plan template was provided to the operator via email.
 
Associated Alerts: TCR-2879 - 10/03/2024 - COLIFORM (TCR)

TCR-2816 - 09/26/2024 - COLIFORM (TCR)



More information for this water system: SDWIS ID 1316
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login