OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 91508
PWS Name: RUCH ELEMENTARY SD 549
 
Who Was Contacted: ANDY CHASTEEN
Contact Phone: 541-842-3646 (Email address hidden)
Contact Date: 07/29/2024
Contacted By: BAIRD, GREGG (DWP)
Contact Method/Location: Email
 
Assistance Type: OTHER WATER QUALITY - UCMR5 PFAS detections
Reasons: Other
 
Details: PFAS sampling conducted as part of the fifth round of the Unregulated Contaminant Monitoring Rule (UCMR5) showed PFOS at 10.6 ppt, PFOA at 9.2 ppt, PFHxS at 33.4 ppt, PFBS at 14.8 ppt, PFPeA at 11.8 ppt, PFPeS at 9.8 ppt, PFHxA at 13.9 ppt, and PFHpA at 3.7 ppt at entry point A (EP-A) EP for Well for a sample collected on 6/17/24. The PFOS, PFOA, and PFHxS results exceed EPA's new MCLs of 4.0 ppt (PFOS & PFOA) and 10 ppt (PFHxS) so system will likely need to take corrective action to comply with MCLs by 2029. A letter was mailed and emailed to the water system on 7/29/24 which included information on how the results compare to the new MCLs, requirements to notify customers of availability of results, and information on Emerging Contaminant funding available to address PFAS.


More information for this water system: SDWIS ID 897
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login