OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 01201 | ||
PWS Name: | SAUNDERS CREEK HOC | ||
Who Was Contacted: | Deb Taylor | ||
Contact Phone: | (Email address hidden) | ||
Contact Date: | 11/29/2024 | ||
Contacted By: | DOWNS, KENT (DWP) | ||
Contact Method/Location: | |||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | Coliform |
||
Details: | TC positive in RT, RPs and TG samples. 11.25.2024- one TG sample and one RP sample came back TC Positive. A request was made via email to the operator to provide an update on corrective actions that the system has done and to confirm if they are still on a voluntary boil advisory. 11.13.2024-System completed a L1 coliform investigation. The operator noted in the report that site No. 33 had a resent septic issue. Site No. 33 is located near the wellhead. The septic issue on site No. 33 was identified as a possible cause for the recent coliform contamination. The operator was advised to collect special samples after completing any corrective actions. 11.12.2024-All three RPs and the TG samples came back positive for TC but negative for E. Coli. The operator posted a voluntary boil water advisory. Next steps: The operator was instructed to complete a Level 1 coliform investigation and email a copy of the boil water advisory. Additionally, the operator is considering shock chlorination of the system, and guidance on this process has been provided. 11.08.2024-The RT sample collected at space No. 14 on 11.06.24, tested positive for TC. The operator was contacted via email and advised to collect 3 RPs and a TG sample at the source. The operator stated that she is planning to collect the follow up samples on 11.11.2024. |
||
Associated Alerts: | TCR-3227 - 11/27/2024 - COLIFORM (TCR) TCR-3228 - 11/27/2024 - COLIFORM (TCR) TCR-3126 - 11/13/2024 - COLIFORM (TCR) TCR-3127 - 11/13/2024 - COLIFORM (TCR) TCR-3124 - 11/13/2024 - COLIFORM (TCR) TCR-3125 - 11/13/2024 - COLIFORM (TCR) TCR-3088 - 11/08/2024 - COLIFORM (TCR) |