OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 01330
PWS Name: DESIRE FOR HEALING, INC
 
Who Was Contacted: Jessica Raphael
Contact Phone: 541-276-7157
Contact Date: 02/14/2019
Contacted By: WORD, AMY (DWP)
Contact Method/Location: Phone
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
 
Details: The water system had been changed from a state regulated water system to a community water system based on population. Because of the new designation, additional sampling requirements were put on the water system. On 5/23/18 the water system collected 5 lead and copper samples. There were three samples that had detections of lead, one of them being over the action level of 15 ppb with a result of 40 ppb. Because of the exceedance, the system was triggered into additional monitoring and testing. Follow up lead and copper samples, water quality parameters and a public notice were distributed.

The system has had difficulty collecting the water samples correctly. The three high samples collected in May 2018 were taken from residences that had been vacant. Water was supposed to be collected from frequently used taps and only be stagnant in the pipes between 8-18 hours.

The system collected a round of samples on 10/2/18 and all were non detect. Another round of samples were collected February 2019. We are waiting to see the results from these samples. A follow up contact report will be done when the results are received to discuss further action required by the water system.
 
Associated Alerts: CHEM7978 - 07/09/2018 - LEAD SUMMARY



More information for this water system: SDWIS ID 3840
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login