OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00537 | ||
PWS Name: | MONMOUTH, CITY OF | ||
Who Was Contacted: | Matt Johnson | ||
Contact Phone: | 503-838-2173 (Email address hidden) | ||
Contact Date: | 05/19/2025 | ||
Contacted By: | HOFELD, EVAN (DWP) | ||
Contact Method/Location: | |||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | Nitrate |
||
Details: | On 5-12-25 an alert was generated for a nitrate result of 9.38 mg/l from sampling completed 5-6-25 at the entry point for the wells (EP-A). The system blends sources to reduce high nitrate levels in the MC Well #1 source (SRC-AA) and has a history of seasonal variations in nitrate (documented in numerous contact reports in the past), but has remained consistently below the MCL of 10 mg/l. On 5-19-25 I received an email from Matt Johnson to let me know that their latest nitrate sample result was 9.38 mg/L. Matt said that they had turned on all blending sources to keep the nitrate levels down as low as possible. They will continue to monitor the levels in-house 3x per week and if they see any high in-house readings, they will send in a sample to the lab to verify. No further action required (other than to continue blending to reduce nitrates). System has been reliably and consistently below the 10 mg/l MCL based on quarterly nitrate sampling since 2005. | ||
Associated Alerts: | NO3-461 - 05/12/2025 - NITRATE |