OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 90861 | ||
PWS Name: | CAMP MYRTLEWOOD | ||
Who Was Contacted: | Josh Danielson | ||
Contact Phone: | (Email address hidden) | ||
Contact Date: | 06/17/2025 | ||
Contacted By: | DOWNS, KENT (DWP) | ||
Contact Method/Location: | |||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | Coliform |
||
Details: | TC positive sample collected on 06.16.2025 06.16.2025-The operator was advised to collect 3 repeat samples today: One at Managers sink No. 1 that tested TC positive, one within 5 connections downstream from the Managers sink No. 1, and one sample within 5 connections upstream from the Managers sink No. 1. Josh believes the recent TC positive sample was the result of not properly sanitizing the sample tap. Repeat samples will be collected later today or tomorrow. Chlorine concentration in the distribution system at the time the sample was collected was 1.3 ppm. Additional information provided to the operator via email: - template for revised coliform sampling plan. -Template for ERP -Template for O&M Manual - link to proper sampling procedure |
||
Associated Alerts: | TCR-3891 - 06/17/2025 - COLIFORM (TCR) |