OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00624
PWS Name: PHILOMATH PUBLIC WORKS
 
Who Was Contacted: Kevin Fear
Contact Phone: 541-929-3579 (Email address hidden)
Contact Date: 04/03/2019
Contacted By: STEVENSON, SHAWN (DWP)
Contact Method/Location: Email
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
 
Details: Kevin Fear emailed OHA tech staff regarding a power outage that stopped pressure pumps and dropped pressure below 20 psi at one of the elevated pressure zones for Starlight Village. The details are included below.

"At about 12:45pm all of Philomath was affected by a large power outage. The City had 3 employees available to respond to the outage. We immediately began shutting off services to homes who are in the 0-25 psi range during a pump failure or power outage. Door hangers were hung on doors where employees got no answer and homeowners who were home were notified both by door hanger and by a City employee explaining the situation and to boil water until further notice. Power was restored to the pump-station about 45 minutes later at about 1:30 pm, and flushing began. Flushing lasted approximately 30-40 minutes. A chlorine residual of .72 was obtained from 470 Melville Crescent and a residual of .68 was obtained from 515 Fawn Lane, the ends of the two mainline runs in Starlight Village. A special coliform sample was taken at the end of each line (Melville Crescent and Fawn Lane) and taken to the lab. Services were turned back on to the affected homes for owners to utilize for sanitary and boiling for consumption. The samples were delivered to the lab at about 3:00 pm Thursday March 28th.

On Friday March 29th at about 1:00pm, the lab confirmed by phone that the results were negative for coliforms and E.coli. Employees went door to door and notified the affected homeowners that the boil water notice is lifted and the water can again be consumed without boiling."
 
Associated Alerts: ALERT IS NOT IN SDWIS YET



More information for this water system: SDWIS ID 3983
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login