OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00262 | ||
PWS Name: | DUNDEE, CITY OF | ||
Who Was Contacted: | Chuck Simpson | ||
Contact Phone: | 503-538-6700 | ||
Contact Date: | 12/03/2018 | ||
Contacted By: | CIVIL WEST ENGINEERS, INC (DWP) | ||
Contact Method/Location: | Field | ||
Assistance Type: | CIRCUIT RIDER ASSISTANCE | ||
Details: | Study the Dundee water system and visit with city operating staff to determine problems with conducting a successful future CT study. 1. Submitted a CT test pre-approval report to OHA, 8/2/18 based on system operating assumptions prior to field visit. 2. Provide HECO memorandum for site visit 8/30/18 (See attached). Summary as follows: a) Tested inflow rate to cemetery reservoir. Altitude valve appears to limit inflow rate too much. b) Used a fire monitor to increase system flow rate. Flow was still below the desired rate. c) Checked chlorine residuals from grab samples using portable analyzers. These might have practical limits for a CT test of limited duration. |