OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00153
PWS Name: BURNS WATER DEPARTMENT
 
Who Was Contacted: Ty Richardson
Contact Phone: (Email address hidden)
Contact Date: 01/26/2026
Contacted By: WORD, AMY (DWP)
Contact Method/Location: Email
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
 
Details: On 12/3/25, the system experienced a total coliform detection. Three repeats and 3 triggered source samples were collected on 12/8/25 with 2 of the repeats and source samples from wells 2 and 3 positive for total coliform. The system followed up with low dose chlorination and flushing of the water system.

On 1/15/26, 3 routine samples were collected and 2 were positive for total coliform. System is to collect 3 repeat samples and triggered source samples from each active well. Ty said not all wells were on at the time, but that he would collect from all 5 wells. At the time of this contact report, the results have not been received from the lab.

The system did find a check valve issue with well 2 and is continuing to determine other possible causes of contamination. Additionally, the city has 2 months of multiple coliform detections. If there is another month with multiple hits in 2026, treatment will be required.
 
Associated Alerts: TCR-5255 - 01/16/2026 - COLIFORM (TCR)

TCR-5254 - 01/16/2026 - COLIFORM (TCR)

TCR-5161 - 12/26/2025 - COLIFORM (TCR)

TCR-5019 - 12/10/2025 - COLIFORM (TCR)

TCR-5020 - 12/10/2025 - COLIFORM (TCR)

TCR-5021 - 12/10/2025 - COLIFORM (TCR)

TCR-5018 - 12/10/2025 - COLIFORM (TCR)



More information for this water system: SDWIS ID 3716
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
PFAS data are now located on the Chemical Results page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Main menu:
Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login