OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00359 | ||
PWS Name: | CORBETT WATER DISTRICT | ||
Who Was Contacted: | Jeff Busto | ||
Contact Phone: | 503-348-9858 | ||
Contact Date: | 05/02/2019 | ||
Contacted By: | BYRD, MICHELLE (DWP) | ||
Contact Method/Location: | Phone | ||
Assistance Type: | OTHER REGULATORY - Monitoring equipment | ||
Reasons: | Operations |
||
Details: | Jeff notified me that the CL17 analyzer after the clearwell normally used for compliance was not working correctly. The CLF10 reagentless analyzer before the clearwell and CL17 analyzer after the 1 MG reservoir are functioning correctly. Until the CL17 analyzer after the clearwell is back online, He will use the CL17 analyzer after the 1 MG reservoir for compliance and apply the contact time in the clearwell to conservatively calculate actual CT. Chlorine residual is targeted above 1 mg/L and CT requirements are being met. He will resume using the CL17 analyzer after the clearwell for compliance once it is back online early next week. |