OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00230
PWS Name: WESLINN WATER COMPANY
 
Who Was Contacted: JOE ANTHONY
Contact Phone: 541-990-9835 (Email address hidden)
Contact Date: 04/22/2026
Contacted By: BAIRD, GREGG (DWP)
Contact Method/Location: Email
 
Assistance Type: OTHER WATER QUALITY - PFAS detects
Reasons: Other
 
Details: PFAS sampling conducted as part of the OHA PFAS Sampling Project PFOS 6.47 ppt, PFOA 6.55 ppt, PFHxS 2.37 ppt, PFBS 51.3 ppt, PFHxA 5.50 ppt, PFPeA 4.96 ppt at entry point A (EP-A) for Well for samples collected on 1/14/26. Although compliance with the MCLs is not yet required, these results indicate that WESLINN WATER COMPANY may eventually exceed the MCLs for PFOS and PFOA. Compliance will be based on a running annual average (RAA). If compliance monitoring beginning April 2027 shows the RAA exceeds the MCLs, the system will need to take corrective action to comply with the MCLs by April 2029. A letter was mailed and emailed to the water system on 4/22/26 which included information on how the results compare to the new PFAS MCLs, PFAS rule initial monitoring requirements, and information on Emerging Contaminant funding available to address PFAS.