OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00465
PWS Name: BANDON/PORT ORFORD KOA
 
Who Was Contacted: CATHY DAVIS
Contact Phone: 503-807-2154 (Email address hidden)
Contact Date: 10/14/2019
Contacted By: DOWNS, KENT (CURRY COUNTY)
Contact Method/Location: Field
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
 
Details: On 10.14.2019 A copy of the L2 investigation report was emailed to DWS Compliance office.

On 10.12.2019 I conducted a L2 investigation to address the recent positive Coli results from the repeat samples collected on 10/09/2019.

Possible cause identified: broken water line in front of the chlorinator shack. The distribution pipe at this location was leaking and the samples were collected before the repairs were completed.

Corrective actions required:
1. Provide a free chlorine DPD testing device.
2. Install a new chlorinator.
3. Replace the garbage container used for mixing chlorine solution with an NSF 61 approved container.
4. Eliminate the gap created by the chord that extends through the top of the well casing.
5. Once all repairs have been completed, disinfect the system. As a reference, consider following the instruction on the DWS Well Disinfection (pdf) technical bulletin for shock chlorinating small distribution systems.

Sistem was also instructed to collect the following samples:
- Collect a triggered sample by 10/20/2019.
- Collect 3 repeat samples by 10/20/2019
- Collect 3 temporary routine samples by 11/30/2019.
 
Associated Alerts: COLI19413 - 10/11/2019 - COLIFORM (TCR)



More information for this water system: SDWIS ID 33
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login