OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00296
PWS Name: FAIRVIEW, CITY OF
 
Who Was Contacted: Derrick Yates
Contact Phone: 503-969-6449
Contact Date: 10/28/2019
Contacted By: BYRD, MICHELLE P (DWP)
Contact Method/Location: Phone
 
Assistance Type: OTHER WATER QUALITY - Chlorine equipment malfunction
Reasons: Chlorine
 
Details: I received a call from Derrick about a chlorine analyzer malfunction resulting in chlorine residual over 4 mg/L at Well 9 (EP-F) this past weekend. False analyzer readings increased chlorine at the injector pump. The problem recognized on Friday and corrected by Saturday lasted less than 24 hours. Chlorine residual have since dropped to 2 mg/L. Distribution waterlines continue to be flushed to lower chlorine residual to 1 mg/L. Chlorine alarms and triggers that failed are being evaluated. Derrick noted a few customer notified the city about the issue.

Chlorine residuals measured with routine coliform distribution samples determines MRDL compliance. September 1st monitoring period shows an annual average of 0.9 mg/L which is below the MCL of 4.0 mg/L for chlorine. No further action needed.


For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3298