PWS ID: OR41 01501
PWS Name: COUNTRY CLUB ESTATES WD
 
Who Was Contacted: JASON WILSON
Contact Phone: 541-297-3371
Contact Date: 11/20/2019
Contacted By: PARRY, BETSY (DWP)
Contact Method/Location: Phone
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Disinfection Byproducts
 
Details: Their November DBP levels are again high. This is the first quarterly sample result after the original 8/29/2019 exceedance (for TTHM). They are collecting the quarterly samples at both of the original IDSE locations- 62112 DOUBLE EAGLE RD and 93621 LINKS LANE.

NOTE: All the residents have a 1000-gal holding tank on their individual properties. For the November sample at Double Eagle Rd, they switched to collecting the sample before the customer's meter (at a "clean-out port"), to avoid the complicating issue of the extra holding tank on their property. But at the Links Lane location, no similar tap was available, so the November Links Lane location was still collected after the water had passed through the 1000-gal holding tank at that residence (after the meter).

The CCE board will be contacting the Circuit Rider for assistance in troubleshooting this issue. The board's plan of action is to test the DBP levels at various locations in the system - as the water arrives from Coos Bay North Bend, after filtration and chlorination but before the regular storage tanks, and at the entry point to the distribution system. They normally maintain a residual at the EP of ~1.0 mg/L. It was suggested they also test the TOC levels as the water arrives from CBNB.

They also mentioned that the storage tanks had never been cleaned out since they switched from the well sources, and there is some brown sludge in the bottom, leftover from that time. It might be good to clean those tanks out to eliminate that variable.

There is no violation until the annual average of 4 quarterly results exceeds the MCL.
 
Associated Alerts: CHEM8698 - 11/20/2019 - TOTAL HALOACETIC ACIDS (HAA5) , TTHM



More information for this water system: SDWIS ID 4894
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login