OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00041 | ||
PWS Name: | AMITY, CITY OF | ||
Who Was Contacted and Phone: | Jason Knope (503) 835-4181 | ||
Contact Date: | 01/17/2006 | ||
Contacted By: | FARRELLY, PETER (DWP) | ||
Contact Method/Location: | Office | ||
Assistance Type: | OTHER REGULATORY - OTHER | ||
Reasons: | Operations N/A |
||
Details: | SUMMARY: Auto Plant Shutdown Reduced Water Supply DETAILS: Chlorine analyzer failed at 10 pm Monday night, triggering the alarm. The automatic alarm successfully shut down the plant, but failed to notify operators of the shutdown. Operators did not become aware of the plant shutdown until ~9 am Tuesday morning. At that time Jason sent operators to test the high points and extremities of the distribution system to ascertain that the minimum water pressure was ~25 psi (above the required 20 psi). Jason then implemented the Water Conservation Plan of the city. Since the 3 schools in town are the biggest users of water, part of the Plan is to close the 3 schools. Schools had a half-day Tuesday. The plant should have no problem producing water to restore the The Circuit Rider, Rob Henry, came out Tuesday to help isolate the problem at |