OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 91964
PWS Name: CAMP YAMHILL
 
Who Was Contacted and Phone: Greg Williams (506) 662-3710
Contact Date: 08/02/2005
Contacted By: CHARBONNEAU, TOM (YAMHILL COUNTY)
Contact Method/Location: Office
 
Assistance Type: DISEASE INVESTIGATION
Reasons: N/A
N/A
 
Details: SUMMARY: Disease Outbreak at the camp. Probably due to conditions around the middle of May 05 ACTION NEEDED: 5-29-05- Conference call with Paul Lewis, Dave L Yamhill County, etc. It was decided that the water supply was the probable cause of the outbreak and the treatment must be upgraded. Until improvements are made the camp must haul drinking water to fill the reservoir. Camp will haul water from the City of Yamhill. 6-1-05 - HBH Engineering was contacted to provide assistance to the camp to resolve problem. 6-2-05 - HBH signed the contact to start work. 6-3-05 - HBH on site at Camp Yamhill. Complete tracer study (find 27 minutes). Evaluate that the DE filter is ineffective. Start working on SSF installation. 6-4-05 - SSF installed, DE is out. 7-1-05 - SSF flowing to waste. 7-4-05-DWP on site to review SSF and collect samples. 7-5-05 - SSF results for TC and EC removal show 94% turbidity at 70% removal. 7-7-05 DWP on site to collect SSF samples. 7-8-05 Results show SSF removal for TC, EC at 98%. Called Camp Yamhill and discussed with Gordy the CT calculations, turbidity monitoring and reporting. With the levels of chlorine residual, pH, temp and contact time, a free residual of 2 ppm will more than meet required CTs. We gave the camp the go-ahead to use the SSF water. 7-25-05 - Visited camp to collect SSF samples. 7-26-05 - Results for the SSF test show removal for TC and EC at 99%. To finish this project we need as-builds from HBH.


More information for this water system: SDWIS ID 4133
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login