OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00821
PWS Name: SILETZ, CITY OF
 
Who Was Contacted and Phone: Allen Middaugh (541) 444-2521
Contact Date: 04/05/2007
Contacted By: KELLEY, KAREN (REGION 2)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Disinfection Byproducts
SWTR
 
Details: SUMMARY: WTP Rating, CCR Assistance, Chem Schedule Update DETAILS: I spoke with Tom Charbonneau today regarding the log inactivation credit assigned to the current wtp at the City of Siletz. The current US Filter Microfloc plant went on-line in 1999-2000 and includes coagulation (alum, polymer and miox pre-treatment), two upflow clarifiers, rapid sand filtration and miox disinfection followed by soda ash for corrosion control. Tom confirmed that the EPA considers this type of package plant to meet conventional filtration requirements. Therefore, the plant is rated at 2.5 log removal credit for giardia and 2.0 credit for crypto. As such, I updated sdwis to show the 2.5 removal rating, added the quarterly schedule for TOC/Alkalinity monitoring and reduced the DBP schedule from quarterly to annual (per reduction rules and last sanitary survey). In addition, I reviewed their draft 2006 consumer confidence report and approved it with one edit. Allen and I discussed the edit and the changes to the chem schedule. Allen agreed to contract with a lab to comply with the TOC/Alkalinity requirements and will sample for 2007 DBPs this summer. ACTION NEEDED: None. Changes to sdwis were made 4/5/2007.


More information for this water system: SDWIS ID 3993
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login