OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00466
PWS Name: LANGLOIS WATER DISTRICT
 
Who Was Contacted and Phone: Dave Terrusa (541) 348-2142
Contact Date: 06/20/2007
Contacted By: STRASSNER, BOB (DWP)
Contact Method/Location: Office
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
Reasons: Operations
N/A
 
Details: SUMMARY: Water system controls and improvements options DETAILS: Langlois has in-plant alarms and critical set points that shut down the plant on high NTUs and low Cl residual. These alarms are not currently tied into a dialer to notify the operator when these incidents occur. Dave had reviewed the water system controls and improvements engineering report provided by the circuit rider programs Terry Nelson in October 2006. The Langlois plant had recently had a shut-down on low chlorine, discovered hours after the incident, resulting in a significant loss of production. The engineering report prioritizes improvement options and alarm notification is noted as being of the highest priority. The ability to pursue other district duties while the water plant runs unattended is important to Dave as the sole operator of the system. I emphasized the need to pursue the recommendations made in the report as a primary option to monitor the treatment process but to install additional alarms for fire and intrusion. Low water alarms at the intake and storage reservoir would also be valuable. Consider a Sensaphone 1108 or 1108RC (USA Bluebook). Installed estimate (excluding phone service and intruder/fire system): $2,500 ACTION NEEDED: Be available with technical assistance if requested in the future by the district.


More information for this water system: SDWIS ID 3963
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login