OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00577 | ||
PWS Name: | NORTH POWDER, CITY OF | ||
Who Was Contacted and Phone: | Mike Gibson (541) 910-5170 | ||
Contact Date: | 08/11/2008 | ||
Contacted By: | GOSS, BILL (DWP) | ||
Contact Method/Location: | Field | ||
Assistance Type: | PLAN REVIEW | ||
Reasons: | Operations N/A |
||
Details: | SUMMARY: Plan Review Inspection DETAILS: Met with new operator Mike Gibson. Inspected polyphosphate treatment system. An LMI model A171-151S feed pump with a max rate of 0.42 GPH is used to inject the All-Qwest 105 blended phosphate. Recommended dosage is 1 mg/L. The feed pump was returned to service this morning after being out of service for a length of time. ACTION NEEDED: PWS to measure and record polyphosphate concentration in the distribution system using a field test kit on a regular basis. |