OHA Drinking Water Services
Contact Report Details |
|||
| PWS ID: | OR41 91852 | ||
| PWS Name: | LAKES EDGE RV PARK | ||
| Who Was Contacted and Phone: | Fred Hilden (541) 997-6056 | ||
| Contact Date: | 09/11/2008 | ||
| Contacted By: | PARRY, BETSY (REGION 2) | ||
| Contact Method/Location: | Office | ||
| Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
| Reasons: | Coliform Coliform |
||
| Details: | SUMMARY: Discussed Next Steps after Positive Repeat TC Results DETAILS: Fred called me with the results. The repeat tests at the well and at the point of entry were negative-- the two tests along the distribution lines were positive. Watermasters advised Fred to shock chlorinate the distribution system, and I agreed. I showed Fred the Tier 2 Public Notice templates on our website. He will fax me the public notice tomorrow. He will retest for TC in the distribution system 3-5 days after chlorinating. ACTION NEEDED: Await fax of public notice and the results of the next sampling after the corrective action has been taken. | ||