OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 91852
PWS Name: LAKES EDGE RV PARK
 
Who Was Contacted and Phone: Fred Hilden (541) 997-6056
Contact Date: 11/12/2008
Contacted By: KALISH, FRED (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
Operations
 
Details: SUMMARY: Contact with Facility Regarding Coliform Detections and Water Treatment System DETAILS: Returned call to Fred Hilden (owner) to discuss new water treatment system and necessary plan review and also recent coliform positives throughout system. In recent water system survey Casey noted new water treatment system (filter, water softener, charcoal filter, nanofilter - 0.2 um) which replaced simple sodium hypochlorite system. Historical problem with excess iron in water. Fred wanted to discuss recent coliform positives. Problems began after new system was installed but not without inconsistencies since the source came up clean on occasion. Sept 3 first positive. Sept 8 2 of 4 were positive. Shock Cl around Sept 16. No positives on Sept 26. Oct 14 positive. Oct 17 3 of 4 positive. Reshocked system. Oct 27 4 of 4 positive. Nov 2 4 of 4 positive, also well head positive. I suggested he have a seasoned sampler sample from wellhead to verify that source is problem. Once determined, probably needs to begin hypochlorite addition as longterm fix as there are no obvious issues with wellhead seal. Also, will send docs to Portland for plan review. ACTION NEEDED: Wait for Coliform results.


More information for this water system: SDWIS ID 1054
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login