OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00851
PWS Name: SWEET HOME, CITY OF
 
Who Was Contacted and Phone: Tim Sanders (541) 451-1117
Contact Date: 10/30/2008
Contacted By: KELLEY, KAREN (REGION 2)
Contact Method/Location: Field
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
N/A
 
Details: SUMMARY: Lead action level exceedance for 9/08 sampling round. DETAILS: I received an alert for a lead action level exceedance on 10/29/08 for samples collected 9/18/08. While on site 10/30/08 for a WTP inspection, I discussed the situation and reviewed the results with the plant operators. One of the samples with the highest lead level was collected from a home undergoing an extensive remodel. The workers at the home did not speak english well and the operator accepted a sample from them that may have been collected from a wellded spigot where the kitchen sink was being replaced. The plant operators will confirm this information and provide it in writing to me asking for sample invalidation due to the improper collection site. They will need to replace this site with an appropriate sample location asap. If this documentation and replacement sample are not provided, the sample will not be invalidated and further follow-up will be required including collection of water quality parameter samples, source samples, public education, and a letter of recommendation for resolution of the lead action level exceedance. ACTION NEEDED: Await documentation requesting sample invalidation and results of replacement sample.


More information for this water system: SDWIS ID 3915
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login