OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00223
PWS Name: WHISPERING PINES MOBILE LODGE
 
Who Was Contacted and Phone: Theron Burgess (541) 738-6906
Contact Date: 10/14/2008
Contacted By: HOY, DEBORAH (LINN COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
Coliform
 
Details: SUMMARY: Total coliform received October 13, 2008 DETAILS: I asked the operator if he was aware that the free chlorine residual reading on the day of the positive coliform sample was 0.0 ppm. He said the residual that was taken that day was 0.2 ppm. He discovered a hole in the chlorine pumps tubing after the positive TC notification and realized that no chlorine was being injected into the system. He has since fixed the pump and shocked the reservoir with 1 gallon of bleach. I advised him to flush the reservoir and take 4 repeats when the chlorine residual I back to a minimum 0.2 ppm in the distribution system by following the CBSP. I asked him to take the 4th repeat sample at the raw sample tap to check on the source water quality as they have been disinfecting for residual maintenance of the redwood reservoir only. I reminded the operator that he is required to monitor and record the chlorine residual within the distribution system on a daily basis, 7 days a week. I asked the operator to provide Linn County EH with a map of the distribution system and to stop by to update the systems coliform bacteria sampling plan. I informed the operator that 5 routine samples are due in November. ACTION NEEDED: Update the coliform bacteria sampling plan.
 
Associated Alerts: COLI5757 - 10/13/2008 - COLIFORM (TCR)



More information for this water system: SDWIS ID 3276
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login