OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00507
PWS Name: MAPLETON WATER DISTRICT
 
Who Was Contacted and Phone: Terry Saubert (541) 268-4348
Contact Date: 09/09/2008
Contacted By: PARMENTER, AMY (REGION 2)
Contact Method/Location: Office
 
Assistance Type: PLAN REVIEW
Reasons: Operations
None
 
Details: SUMMARY: new membrane filtration update DETAILS: Mapleton WD replaced their existing filtration with membrane filtration and installed on-site chlorine generation. Their membrane filtration is credited with 2.5-log Giardia removal, and so they must provide 0.5-log with chlorine. The design flow of the plant is 280 gpm and the max will be 210. The as-builts are not finished yet, but the plant has been providing drinking water to the public for about a month. I asked Tom Charbonneau if this is ok and he said it is. The chlorine residuals and turbidity measurements are good. The as-builts will be sent to the DWP in a month. A tracer study will be completed. ACTION NEEDED: Await final approval letter from Plan Review Engineer and tracer study results. Conduct plan review inspection after final approval.