OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00991 | ||
PWS Name: | GRANDVIEW MOBILE HOME PARK | ||
Who Was Contacted and Phone: | Howard James (541) 998-8296 | ||
Contact Date: | 04/17/2009 | ||
Contacted By: | PARMENTER, AMY (REGION 2) | ||
Contact Method/Location: | Office | ||
Assistance Type: | VIOLATION RESPONSE | ||
Reasons: | Lead or Copper None |
||
Details: | SUMMARY: Corrosion Control for Lead Exceedance DETAILS: I have set the minimum pH for corrosion control at 7.2 with a goal of 7.3-7.4. HBH Engineers said that higher pHs were resulting in higher copper at one home. A letter and corrosion control forms were sent to Howard James on 4/2/09 and I spoke to him on 4/17/09. He understands the requirements and said that Tom Charbonneau also sent him a letter and Howard also understands what still needs to be sent to Tom for Plan Review. ACTION NEEDED: Await final plan review approval. |