OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 95337 | ||
PWS Name: | FRY FOODS | ||
Who Was Contacted: | Hector Herrera | ||
Contact Phone: | (Email address hidden) | ||
Contact Date: | 11/17/2017 | ||
Contacted By: | NEY, MELISSA (DEPT OF AGRICULTURE) | ||
Contact Method/Location: | |||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | Arsenic |
||
Details: | The chemical alert relates to the Arsenic Level. The maximum limit is 10 and the sample from Fry Foods was 14. This was due to the IOC sample not being taken from the hand washing sink that has the arsenic unit on it. IOC’s include the arsenic test. In the future the IOC sample will be collected at the hand washing sink that has the Arsenic unit on it. Since we have results from the two hand washing sinks with the arsenic units on them e do not need a resample. The other two samples were within limits. The sodium is a non-alert and is a non-regulated item but it is still tested. So this is an FYI that your water is high in sodium. |
||
Associated Alerts: | CHEM7772 - 11/16/2017 - ARSENIC , SODIUM |