OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00802
PWS Name: ARCH CAPE WATER DISTRICT
 
Who Was Contacted and Phone: Thomas Merrell (503) 436-2790
Contact Date: 09/11/2009
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Disinfection Byproducts
DBPs
 
Details: SUMMARY: TTHM and HAA5 RAA MCL Exceeded DETAILS: With results of their 3rd quarter 2009 DBP sampling completed on August 27, 2009, the running annual average (RAA) for the period between Oct 1, 2008 and Sept 30, 2009 for TTHM was 0.0890 mg/l and the RAA for HAA5 was 0.1007 mg/l, both of which exceeded the DBP MCLs of 0.080 and 0.060 mg/l, respectively. I called a left a message for Thomas notifying him that a 30-day public notice would be needed for both TTHM and HAA5, since the TTHM MCL was a new exceedance (not exceeded since 2007) and that he would need to include the relevant health effects language for both TTHM and HAA5. The system is soon to be in a bilateral compliance agreement with DWP to resolve the DBP MCLs and had been conducting quarterly public notice for routine HAA5 exceedances. ACTION NEEDED: System to issue Tier 2 public notice within 30 days of October 1, 2009 for the TTHM and HAA5 RAA MCL exceedances, including the relevant health effects language.
 
Associated Alerts: CHEM3665 - 09/08/2009 - TOTAL HALOACETIC ACIDS (HAA5) , TTHM

CHEM3665 - 09/08/2009 - TOTAL HALOACETIC ACIDS (HAA5) , TTHM



More information for this water system: SDWIS ID 3909
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login